Settings

The room

The working plane is the height the light has to arrive at: 0.85 m for a desk, 0.0 for a floor, higher for a bench. The mounting height the room index uses is measured from there, not from the floor.

The fitting, and the two factors

The utilisation factor comes from the fitting’s own table, read against the room index and the reflectances of the ceiling, walls and floor. The target illuminance comes from the table for the task. Neither is invented here.

The layout

Step by step

The working


    
How it works

LUX works out how many light fittings a room needs to reach a target light level. It uses the utilisation factor, which can vary from under a third in a tall dark room to over two thirds in a low white one, and designs for a room as it will be once dirty. It gives the number of fittings and checks the spacing against the mounting height. The figures stay in this tab.